Wire Size Calculator

Enter your load in watts to see what mm² copper wire and breaker you need. E.g. 2000 W needs 2.5 mm² wire with a 16A breaker.

W

Add up the watts of everything running together

V

Homes in Bangladesh use 220 volts (enter 100–250)

m

One-way distance from meter to switchboard — drop counts go-and-return

0.8 with motors, 1 for lights-fans-heaters only (0.5–1)

Recommended copper wire

2.5 mm²

Load current
11.36 A
Recommended copper wire
2.5 mm²
Circuit breaker (MCB)
16 A
Voltage drop
1.42%
Safety margin
25% extra over current (14.2 A)

Use 2.5 mm² copper wire (PVC/FR) with a 16 A MCB breaker.

This is guidance only — wiring must be done by a licensed electrician; overloading can cause fire.

How this was calculated
  1. Current = 2,000 ÷ (220 × 0.8) = 11.36 A
  2. Design current with 25% margin = 11.36 A × 1.25 = 14.2 A
  3. Thinnest copper wire carrying 14.2 A = 2.5 mm² (up to 18 A)
  4. Standard breaker at or above 14.2 A = 16 A
  5. Voltage drop = 2 × length × current × 0.0172 ÷ size ÷ voltage = 1.42% (keep under 3%)

How to use

  1. Enter the total watts of everything running together.
  2. Give voltage (220 at home), distance from meter (metres) and power factor (0.8 with motors).
  3. The result shows wire size, breaker and voltage drop — always hire an electrician for the work.

Formula

Current = load (watts) ÷ (voltage × power factor) Design current = current × 1.25 (25% safety margin) Wire size = thinnest copper wire that can carry the design current Breaker = standard MCB at or above the design current

  • Homes in Bangladesh run on single-phase 220 volts.
  • Voltage drop = 2 × length × current × 0.0172 ÷ size ÷ voltage — keep it under 3%.

Wire size table (copper, PVC)

Wire size Max current Typical use
1.5 mm² 13A Light and fan points
2.5 mm² 18A Fridge, geyser, motor (socket lines)
4 mm² 24A AC (1–1.5 ton), heavy sockets
6 mm² 31A Large AC, sub-main lines
10 mm² 42A Main line, meter to DB board

⚠️ These ratings are deliberately conservative — shop catalogues may print higher numbers. If you land on the borderline, always go one size thicker.

Worked example

2000 W load, 220 V, power factor 0.8, 20-metre run:

Current = 2000 ÷ (220 × 0.8) = 11.36A. Design current = 11.36 × 1.25 = 14.2A. 1.5 mm² (13A) falls short, so use 2.5 mm² wire with a 16A MCB. Drop = 2 × 20 × 11.36 × 0.0172 ÷ 2.5 ÷ 220 = ≈1.4% — safe.

⚠️ Safety

  • This is guidance only — wiring must be done by a licensed electrician; overloading can cause fire.
  • Too much load on thin wire heats it, melts the insulation and causes short circuits.
  • Never fit a bigger breaker than needed — the wire will burn before the breaker trips.
Details: why voltage drops

Wire itself has some resistance (copper: 0.0172 ohm·mm²/m). The higher the current, or the longer/thinner the wire, the more voltage is “spent” along the way — the far end may get 210 or 200 V instead of 220. Under-voltage makes motors draw more current, overheat and die early.

The formula doubles the length because current travels both wires — out and back. If drop exceeds 3%, go one wire size thicker.

Frequently asked questions

What is the difference between RM and solid wire?

RM (stranded) wire has many thin copper strands — flexible, easy to bend, the standard for concealed home wiring. Solid wire has one thick core — stiff and can crack when bent. At the same mm² both carry about the same current.

MCB or fuse — which should I install?

Install an MCB for new wiring. A blown fuse must be replaced, and people often wrap thicker wire around it — which removes all protection. An MCB just needs its switch flipped back, and a correctly rated one trips on overload by itself.

When does an old house need rewiring?

Rewire if the wiring is 20–25 years old aluminium or thin wire, fuses blow or breakers trip often, wires feel hot, or you smell burning. After adding a fridge, AC or geyser, do not load the old 1.5 mm² line — run a separate circuit.

What wire size does a 2000 W geyser need?

2000 ÷ (220 × 0.8) = 11.36 A. With 25% margin that is 14.2 A — so 2.5 mm² copper wire (18A) with a 16A MCB. 1.5 mm² (13A) is not enough.

What happens if voltage drop is too high?

Far rooms get slow fans, dim lights and hot motors. If drop exceeds 3%, use one size thicker wire or split the load into a separate circuit.

Also searched as

wire size calculator · cable size calculator bangladesh · copper wire amp rating chart · mcb size selection · voltage drop calculation